Loopd Port Reset - Siemens SCALANCE XM-400 Configuration Manual

Simatic net industrial ethernet switches command line interface (cli)
Hide thumbs Also See for SCALANCE XM-400:
Table of Contents

Advertisement

Diagnostics
12.3 Loop detection
Parameter
detect-threshold
integer
reaction-timeout
seconds
If you do not select any parameters from the parameter list, the default value is used. The
default values apply only to a port enabled earlier with
Result
The settings are suitably configured.
Further notes
You can display the status of this function and other information with the
command.
12.3.3.3

loopd port reset

Description
With this command, you enable a port that was blocked by loop detection.
Requirement
● Loop detection is enabled
● You are in the Interface configuration mode.
The command prompt is:
cli(config-if-$$$)#
Syntax
Call the command without parameters:
loopd port reset
918
Description
Keyword for the threshold value
Specifies the threshold value after how
many received loop detection frames, a
loop is assumed and the device reacts
according to the setting.
Keyword for the time to the end of the
reaction time
Specifies the number of seconds after
which the device automatically chang-
es to the status in which it was before
the loop.
SCALANCE XM-400/XR-500 Command Line Interface (CLI)
Range of values / note
-
1 ... 500
Default: 2
-
0 ... 86400
Default: 0
If you set the value "0", you need
to enable the port manually again
following a loop using the com-
mand
loopd port reset
.
loopd sender
Configuration Manual, 06/2016, C79000-G8976-C252-11
.
show loopd