FujiFilm CR-IR341 Service Manual page 154

Fuji computed radiography
Table of Contents

Advertisement

C
1
2
ONTENTS
(6) Sequence of After-Reading Conveyance
This is for the operation of the after-reading conveyor and erasure conveyor.
In this sequence, the IP that has been read is fed into the conveyance inverting stocker via
the after-reading conveyor and erasure conveyor.
Fig. 2.7.6 After-Reading Conveyance
The actuations of the
sensors during normal
operation are as follows:
SF2: OPEN
SF4: OPEN
Monitoring of SF4 is
implemented in case SF2
becomes faulty.
Table 2.7.6a Operation Parameters
Symbol
Description
PE21
Conveyance (after-reading conveyance)
PF11
Conveyance (after-reading conveyance)
TF11
After-reading conveyance IP leading-edge detection timeout
Table 2.7.6b Operation Parameters
Symbol
After-reading conveyance IP trailing-edge detection timeout
TF12
009-051-04
05.31.99 FM2460
3
4
5
6
Preprocessing: Fig. 2.7.1, and Fig. 3.3.1
START
After-reading conveyance driving
DRIVE (ME2/PE21)
DRIVE (MF1/PF11)
Is SF1 closed within TF11?
N
Y
Does SF4 remain closed
during TF12?
N
Y
CLOSE
CLOSE
Is SF2 opened?
N
Y
After-reading conveyance stop
DRIVE (ME2/OFF) (soft)
DRIVE (MF1/OFF) (hard)
SF4 normal?
N
Y
END
Description
CR-IR341 Service Manual
7
8
9
10
After-reading conveyance stop
DRIVE (ME2/OFF) (soft)
DRIVE (MF1/OFF) (soft)
MF1, ME2 excitation OFF
Level 0 error
Conveyance error
03D1
(after-reading conveyance)
After-reading conveyance stop
DRIVE (ME2/OFF) (soft)
DRIVE (MF1/OFF) (soft)
MF1, ME2 excitation OFF
Level 0 error
03D2
Conveyance error
(Switchback)
Level 2 error
23D2
Conveyance sensor error
Value
- infinite P
- infinite P
2.67 sec
TR1H0036.EPS
14x17 I
14x14 I
10x12 I
8x10 I
3.17 sec
3.01 sec
2.9 sec
2.68 sec
MD - 91
FR1H0364.EPS
18x24 ST
24x30 ST
18x24 HR
24x30 HR
2.63 sec
2.89 sec
2.63 sec
TR1H0037.EPS
MD - 91
2.76 sec