Chapter 4: Connecting External Equipment (Optional)

Before Connecting Equipment to Feature Port

Connecting Asset Management Strips

62
You can add a DPX2 sensor package to the end of such a sensor-mixing chain if
needed. See
Connecting a DPX2 Sensor Package to DX2, DX or DPX3
50).
PX3TS models have a cap plugged into the FEATURE port when shipping out of
the factory. The cap is intended to protect the port from connecting to
inappropriate equipment. Remove this cap when you need to connect
equipment to this port.
To remove the RJ-45 cap from the FEATURE port:
1.
Locate the port labeled FEATURE.
2.
Remove the cap.
You can remotely track the locations of up to 64 IT devices in the rack by
connecting asset management strips (asset strips) to the PX3TS after IT devices
are tagged electronically.
To use the asset management feature, you need the following items:
Raritan asset strips: An asset strip transmits the asset management tag's ID
and positioning information to the PX3TS.
Raritan asset tags: An asset management tag (asset tag) is adhered to an IT
device. The asset tag uses an electronic ID to identify and locate the IT
device.
Warning: DX-PD2C5 or DX2-DH2C2, and asset management strip(s) are
mutually exclusive so do NOT connect both of them to the PDU
simultaneously.