666
Using Default Thresholds
This command determines whether default thresholds, including the
deassertion hysteresis and assertion timeout, are applied to a specific
environmental sensor.
config:#
externalsensor <n> useDefaultThresholds <option>
Variables:
<n> is the ID number of the environmental sensor that you want to
configure. The ID number is available in the PX3TS web interface or using
the command "show externalsensors <n>" in the CLI. It is an integer
starting at 1.
<option> is one of the options: true or false.
Option
Description
true
Default thresholds are selected as the threshold option
for the specified sensor.
false
Sensor-specific thresholds are selected as the threshold
option for the specified sensor.
Setting the Alarmed to Normal Delay for DX-PIR
This command determines the value of the Alarmed to Normal Delay setting
for a Raritan presence detector.
config:#
externalsensor <n> alarmedToNormalDelay <time>
Variables:
<n> is the ID number of the environmental sensor that you want to
configure. The ID number is available in the PX3TS web interface or using
the command "show externalsensors <n>" in the CLI. It is an integer
starting at 1.
<time> is an integer number in seconds, ranging between 0 and 300.
Examples
This section illustrates several environmental sensor configuration examples.