Off and Lock Icons for Outlets
This section further explains the following two icons for outlets, which display
in the load shedding mode.
Lock icon
: It means the outlet WILL be automatically powered on after
deactivating the load shedding mode.
Off icon
: It means the outlet will remain powered OFF when
deactivating the load shedding mode.
Which outlets show the lock icon
Non-critical outlets that were powered ON prior to the load shedding
mode
Non-critical outlets that you manually switch on during the load shedding
mode
Note: The switching-on operation does not power on the selected
non-critical outlets while the load shedding mode is active, but will cause
those outlets to be automatically turned on after disabling the load
shedding mode.
Which outlets show the Off icon
Any outlets, critical or non-critical, that were powered OFF prior to the
load shedding mode
Any outlets, critical or non-critical, that you manually switch off during the
load shedding mode