Chapter 3: Initial Installation and Configuration
40
Other sensor restrictions when door handles are present:
First make sure the connection of door handles complies with the above
restrictions.
The following restrictions apply only to the PDU that has all the door handles
connected.
•
When there are 2 door handles connected to the PDU (via DX2-DH2C2 or
DX-PD2C5), up to 10 sensor packages of DPX/DPX2/DPX3/DX2 or up to 2
additional DX sensor packages can be additionally connected. Raritan's
sensor hubs must NOT be used.
•
When there is only 1 handle connected, up to 12 sensor packages of
DPX/DPX2/DPX3/DX2 or up to 3 DX sensor packages can be additionally
connected. Raritan's sensor hubs must NOT be used.
NO physical changes made to the number of connected sensor packages:
•
After either PDU enters the power-sharing mode, you must NOT physically
remove or add any environmental sensor packages to BOTH PDUs.
Warning: The in-rush current of a newly added sensor package may cause
both PDUs to reboot.
For information on Raritan's sensor packages or hubs, see
Environmental Sensor Packages
(on page 41).
Connecting Raritan