config:#
sensor outlet <n> <sensor type> assertionTimeout <as_value>
Variables:
<n> is the number of the outlet that you want to configure.
<sensor type> is one of the following sensor types:
Sensor type
current
voltage
activePower
apparentPower
powerFactor
activeEnergy
lineFrequency
Note: If the requested sensor type is not supported, the "Sensor is not
available" message is displayed.
<option> is one of the options: enable, disable or a numeric value.
Option
Description
enable
Enables the specified threshold for a specific outlet
sensor.
disable
Disables the specified threshold for a specific outlet
sensor.
A numeric value
Sets a value for the specified threshold of a specific
outlet sensor and enables this threshold at the same
time.
<hy_value> is a numeric value that is assigned to the hysteresis for the
specified outlet sensor. See
page 839).
<as_value> is a number in samples that is assigned to the assertion
timeout for the specified outlet sensor. See
Timeout
(on page 837).
Chapter 9: Using the Command Line Interface
Description
Current sensor
Voltage sensor
Active power sensor
Apparent power sensor
Power factor sensor
Active energy sensor
Line frequency sensor
"To De-assert" and Deassertion Hysteresis
"To Assert" and Assertion
(on
673