The following procedure illustrates a DPX2 sensor cable with three head
connectors. Your sensor cable may have fewer head connectors.
Warning: If there are free head connectors between a DPX2 sensor cable's
RJ-12 connector and the final attached DPX2 sensor package, the sensor
packages following the free head connector(s) on the same cable do NOT
work properly. Therefore, always occupy all head connectors prior to the
final sensor package with a DPX2 sensor package.
To connect DPX2 to the PX3TS:
1.
Connect a DPX2 sensor package to the first head connector of the DPX2
sensor cable.
2.
Connect remaining DPX2 sensor packages to the second and then the third
head connector.
Tip: If the number of sensors you are connecting is less than the number of
head connectors on your sensor cable, connect them to the first one or first
two head connectors to ensure that there are NO free head connectors
prior to the final DPX2 sensor package attached.
3.
Use an RJ-12 to RJ-45 adapter to connect the DPX2 sensor package(s) to
the PX3TS.
a.
Connect the adapter's RJ-12 connector to the DPX2 sensor cable.
b. Connect the adapter's RJ-45 connector to the RJ-45 SENSOR port of
the PX3TS.
Chapter 4: Connecting External Equipment (Optional)