The active energy sensor is reset.
For example, when the Inlet I1's voltage exceeds the upper warning
threshold, the SNMP notifications are sent, and when the voltage drops
below the upper warning threshold, the SNMP notifications are sent again.
Sample Environmental-Sensor-Level Event Rule
This section applies to outlet-switching capable models only.
In this example, we want PX3TS to activate the load shedding function when a
contact closure sensor enters the alarmed state. This event rule requires
creating a new action before creating the rule.
Step 1: create a new action for activating the load shedding
1.
Choose Device Settings > Event Rules >
2.
In this illustration, assign the name "Activate Load Shedding" to the new
action.
3.
In the Action field, select "Change load shedding state."
4.
In the Operation field, select "Start load shedding."
5.
Click Create to finish the creation.
Chapter 7: Using the Web Interface
.
433