Resetting The Px3Ts; Restarting The Pdu; Resetting Active Energy Readings - LEGRAND Raritan PX3TS User Manual

Transfer switch
Table of Contents

Advertisement

Chapter 9: Using the Command Line Interface

Resetting the PX3TS

704
4.
A message appears, indicating that the specified user was unblocked
successfully.
You can reset the PX3TS to factory defaults or simply restart it using the CLI
commands. In addition, you can reset active energy readings via CLI.
All of these commands begin with reset.

Restarting the PDU

This command restarts the PX3TS. It is not a factory default reset.
To restart the PX3TS:
1.
Ensure you have entered administrator mode and the # prompt is
displayed.
2.
Type either of the following commands to restart the PX3TS.
#
reset unit
-- OR --
#
reset unit /y
3.
If you entered the command without "/y" in Step 2, a message appears
prompting you to confirm the operation. Type y to confirm the reset.
4.
Wait until the reset is complete.
Note: Device reset will cause CLI communications over an "USB" connection to
be lost. Therefore, re-connect the USB cable after the reset is complete.

Resetting Active Energy Readings

You can reset either one active energy sensor or all active energy sensors at a
time to restart the energy accumulation process.
Only users with the "Admin" role assigned can reset active energy readings.
To reset all active energy readings of the PX3TS:
#
reset activeEnergy pdu
-- OR --
#
reset activeEnergy pdu /y
To reset one inlet's active energy readings:
#
reset activeEnergy inlet <n>
-- OR --
#
reset activeEnergy inlet <n> /y