Supported Sensor Configurations For Power Sharing - LEGRAND Raritan PX3TS User Manual

Transfer switch
Table of Contents

Advertisement

Supported Sensor Configurations for Power Sharing

All information and restrictions described in this section apply to BOTH PDUs
involved in the power-sharing configuration, unless otherwise specified.
There are no limitations for connecting Raritan's DPX or DPX2
environmental sensor packages to an iX7
See
DPX Sensor Packages
48).
The maximum number of supported DPX3 environmental sensor packages
remains unchanged -- that is, 12 DPX3 packages. See
Packages
(on page 46).
The maximum number of supported DX environmental sensor packages
also remains unchanged as long as the DPX3-ENVHUB4 sensor hub is not
used -- that is, 12 DX sensor packages. See
45).
The maximum number of supported DX2 environmental sensor packages
remains unchanged -- that is, 12 DX2 packages. See
(on page 43).
However, there are DX restrictions when DPX3-ENVHUB4 is used, and there are
also door handles-related restrictions.
DX sensor restrictions while DPX3-ENVHUB4 is involved:
A maximum of one DPX3-ENVHUB4 and a maximum of 10 DX sensor
packages are supported.
Door handle connection restrictions (via DX2-DH2C2 or DX-PD2C5):
(Restriction only for DX2-DH2C2 manufactured before 2019) DO NOT
connect any "SouthCo H3-EM series" door handle(s) because of insufficient
power supply in the power-sharing mode.
Note: The latest generation of DX2-DH2C2 does NOT have this restriction
and can have SouthCo H3-EM series connected in the power-sharing mode.
A maximum of 2 door handles connected to a maximum of one
DX2-DH2C2 or one DX-PD2C5 package are supported.
All of the 2 door handles must be controlled by the same PDU so that you
can have "only one" handle opened at a time to avoid critical power
consumption. That is, ALL door handles must be connected to only one
PDU in the power-sharing connection, NOT both PDUs.
Note: It is strongly suggested to check and make sure the upper limit of
"powered cry contact actuators" is set to 1 when making a power-sharing
connection. See
Peripherals
Chapter 3: Initial Installation and Configuration
PDU in the power-sharing mode.
(on page 51) or
DPX2 Sensor Packages
DX Sensor Packages
(on page 258).
(on page
DPX3 Sensor
(on page
DX2 Sensor Packages
39

Advertisement

Table of Contents
loading

Table of Contents