LEGRAND Raritan PX3TS User Manual page 221

Transfer switch
Table of Contents

Advertisement

Message
Overload Detected
Internal Fault
Note: In the "off" state, neither inlet on the Transfer Switch page shows the
icon.
Inlet Phase:
Field
Inlet Phase Sync
Inlet Phase Angle
Status
An overload is present.
▪ When the PX3TS device detects an overload
condition on the outlet, it shuts down the outlet
completely to protect the inlets.
▪ The state of the switch remains off as long as the
overload alarm is present.
▪ The load will restore power after performing both
actions below:
Resolve the overload problem.
Manually clear the overload alarm by
performing a manual transfer. To clear the
alarm, see
Manual Transfer When an Alarm
is Present
(on page 114).
A switch open or switch short fault is detected on the
Inlet 1/2 switch.
Description
Indicates whether the phase angles of both inlets
are in synchronization or not.
in sync: The inlets are in synchronization
when their phase angle difference does NOT
exceed 15 degrees.
out of sync: The inlets are out of
synchronization when their phase angle
difference is over 15 degrees.
The 15-degree threshold is not
user-configurable, and it is not related to the
warning/critical thresholds of the 'Inlet Phase
Angle' sensor.
Indicates the value of phase angle difference,
which is the phase shift between the two inlets'
voltage signals.
Chapter 7: Using the Web Interface
201

Advertisement

Table of Contents
loading

Table of Contents