LEGRAND Raritan PX3TS User Manual page 468

Transfer switch
Table of Contents

Advertisement

Chapter 7: Using the Web Interface
448
Field
Number of successful
pings to enable feature
Wait time after
successful ping
Wait time after
unsuccessful ping
Number of consecutive
unsuccessful pings for
failure
Wait time before
resuming pinging after
failure
Number of consecutive
failures before
disabling feature (0 =
unlimited)
5.
On a PDU with outlet switching capability, there is one more checkbox
available -- Power control enabled.
To be able to shut down and power control the monitored IT device via the
Server Reachability page, enable this checkbox and configure related
settings, which are explained in the following table.
6.
Click Create.
7.
To add more IT devices, repeat the same steps.
Description
The number of successful pings required to
declare that the monitored equipment is
"Reachable." Valid range is 0 to 200.
The wait time before sending the next ping if
the previous ping was successfully responded.
Valid range is 5 to 600 (seconds).
The wait time before sending the next ping if
the previous ping was not responded. Valid
range is 3 to 600 (seconds).
The number of consecutive pings without any
response before the monitored equipment is
declared "Unreachable." Valid range is 1 to
100.
The wait time before the PX3TS resumes
pinging after the monitored equipment is
declared "Unreachable." Valid range is 1 to
1200 (seconds).
The number of times the monitored equipment
is declared "Unreachable" consecutively before
the PX3TS disables the ping monitoring feature
for it and shows "Waiting for reliable
connection." Valid range is 0 to 100.