Chapter 7: Using the Web Interface
196
To configure power quality settings:
1.
Click Edit Power Quality Parameters.
2.
Configure the power quality thresholds of both inlets. For details, see
Power Quality Settings
Note: Any changes made to power quality thresholds will change the voltage
and frequency threshold values of both inlets. See
page 218).
To configure inlet phase angles settings (optional):
If thresholds for inlet phase angle difference are enabled/configured, the PX3TS
reports its values and states whenever a specific threshold is hit. For example,
if the upper warning threshold is enabled and reached, you will see the upper
warning alarm and values of inlet phase angle difference in the Dashboard's
Alerted Sensors list or event log. These threshold values do not affect phase
sync detection or transfers/retransfers.
1.
Click
.
2.
Select Threshold Setup. The "Edit Thresholds for Inlet Phase Angle" dialog
appears.
3.
Make changes as needed.
To enable any threshold, select the corresponding checkbox.
(on page 205).