Chapter 7: Using the Web Interface
226
Type a new value in the accompanying text box.
For concepts of thresholds, deassertion hysteresis and assertion timeout,
see
Sensor Threshold Settings
6.
Click Save.

Setting Outlet Power-On Sequence and Delay

By default, outlets are sequentially powered on in the ascending order from
outlet 1 to the final when turning ON or power cycling all outlets on the PX3TS.
You can change the order in which the outlets power ON. This is useful when
there is a specific order in which some IT equipment should be powered up
first.
In addition, you can make a delay occur between two outlets that are turned
on consecutively. For example, if the power-on sequence is Outlet 1 through
Outlet 8, and you want the PX3TS to wait for 5 seconds before turning on
Outlet 4, after Outlet 3 is turned on, assign a delay of 5 seconds to Outlet 3.
To set the outlet power-on sequence:
1.
On the Outlets page, click
2.
Select one or multiple outlets by clicking them one by one in the 'Outlet'
column.
3.
Click the arrow buttons to change the outlet positions.
Button
Function
Top
(on page 834).
> Sequence Setup.