Chapter 9: Using the Command Line Interface
config:#
sensor externalsensor <n> <sensor type> hysteresis <hy_value>
config:#
sensor externalsensor <n> <sensor type> assertionTimeout <as_value>
676
Set the assertion timeout for an environmental sensor:
Variables:
•
<n> is the ID number of the environmental sensor that you want to
configure. The ID number is available in the PX3TS web interface or using
the command "show externalsensors <n>" in the CLI. It is an integer
starting at 1.
•
<sensor type> is one of the following numeric sensor types:
Sensor types
absoluteHumidity
relativeHumidity
temperature
airPressure
airFlow
vibration
Note: If the specified sensor type does not match the type of the specified
environmental sensor, this error message appears: "Specified sensor type
'XXX' does not match the sensor's type (<sensortype>)," where XXX is the
specified sensor type, and <sensortype> is the correct sensor type.
•
<option> is one of the options: enable, disable or a numeric value.
Option
Description
enable
Enables the specified threshold for a specific
environmental sensor.
Disables the specified threshold for a specific
disable
environmental sensor.
A numeric value
Sets a value for the specified threshold of a specific
environmental sensor and enables this threshold at
the same time.
Description
Absolute humidity sensors
Relative humidity sensors
Temperature sensors
Air pressure sensors
Air flow sensors
Vibration sensors