Chapter 7: Using the Web Interface
400
Log an Event Message
The option 'Log event message' records the selected events in the internal log.
The default log message generated for each type of event is available in the
section titled
Default Log Messages
Shut down a Server and Control its Power
The "Power control server" action is available only when your PX3TS is
outlet-switching capable.
You can configure the PX3TS to shut down a specific server and then turn off its
outlet(s), or turn on that server's outlet(s) after a certain event occurs.
The only restriction is a server must be one of the servers being monitored by
your PX3TS and the same PX3TS supplies power to it. To have any server
monitored, see
Monitoring Server Accessibility
Tip: If the server has multiple power cords, make sure all of its power cords are
connected to the same PX3TS and you have created an outlet group for
controlling all outlets simultaneously. See
Operation:
1.
Choose Device Settings > Event Rules >
2.
Select 'Power control server' from the Action list.
3.
In the Operation field, select an action for the server.
Power up: Turns on the outlet or outlet group associated with the
selected server.
Graceful shutdown: Shuts down the selected server first and then turn
off its associated outlet or outlet group.
4.
Select the server you want in the Server field.
If PX3TS cannot power control any server, a message 'Power control
not configured' is shown in the end of the server's host name or IP
address.
(on page 381).
(on page 447).
Outlet Groups
(on page 239).
.