config:#
ts powerQualityParameters frequencyAssertionTimeout <freq_timeout>
Variables:
<threshold_volts> is an integer number up to 500 in Volt.
<volt_hysteresis> is an integer number up to 500 in Volt.
<volt_timeout> is an integer number up to 100 in seconds.
<threshold_Hz> is either an integer number or a number with one decimal
digit in Hz.
<freq_hysteresis> is either an integer number or a number with one
decimal digit in Hz.
<freq_timeout> is an integer number up to 100 in seconds.
Example
The following command sets the Upper Critical voltage threshold to 250 volts
and Lower Warning frequency threshold to 45 Hz.
config:#
ts powerQualityParameters upperCriticalVoltage 250
lowerWarningFrequency 45

PDU Configuration Commands

One PDU configuration command begins with pdu. You can use the PDU
configuration commands to change the settings that apply to the whole PX3TS
device.
Configuration commands are case sensitive so ensure you capitalize them
correctly.
Changing the PDU Name
This command changes the device name of PX3TS.
config:#
pdu name "<name>"
Variables:
<name> is a string comprising up to 64 ASCII printable characters. The
<name> variable must be enclosed in quotes when it contains spaces.