Mode
None
Bridging
Port Forwarding
Tip: If selecting Port Forwarding, the Device Information page will show a
list of port numbers for all cascaded devices. Simply choose Maintenance >
Device Information > Port Forwarding.
5.
For the Port Forwarding mode, one to two more fields have to be
configured.
Note that if either setting below is incorrectly configured, a networking
issue occurs.
Field
Port forwarding role
(available on all cascaded
devices)
Downstream interface
(available on the maser
device only)
6.
(Optional) Configure the network settings by clicking the BRIDGE,
ETH1/ETH2, or WIRELESS section on the same page.
In the Bridging mode, each cascaded device can have different network
settings. You may need to configure each device's network settings in
the BRIDGE section.
In the Port Forwarding mode, all cascaded devices share the master
device's network settings. You only need to configure the master
device's network settings in the ETH1/ETH2 and/or WIRELESS section.
See
Wired Network Settings
(on page 317)
Chapter 7: Using the Web Interface
Description
No cascading mode is enabled. This is the default.
Each device in the cascading chain is accessed
with a different IP address.
Each device in the cascading chain is accessed
with the same IP address(es) but with a different
port number assigned.
For details on port numbers, see
Syntax
(on page 332).
Description
Master or Slave.
This is to determine which device is the
master and which ones are slave devices.
USB or ETH1/ETH2.
This is to determine which port on the
master device is connected to Slave 1.
If ETH1 or ETH2 is selected as the
downstream interface, make sure the
selected Ethernet interface is enabled.
(on page 311) or
Wireless Network Settings
Port Number
329