LEGRAND Raritan PX3TS User Manual page 593

Transfer switch
Table of Contents

Advertisement

Setting the Outlet Initialization Delay
This section applies to outlet-switching capable models only.
This command determines the outlet initialization delay timing on device
startup. See
PDU
(on page 206) for information on outlet initialization delay.
config:#
pdu outletInitializationDelayOnDeviceStartup <timing>
Variables:
<timing> is a delay time between 1 and 3600 seconds.
Note: This feature does NOT take effect and cannot be configured on a PX3TS
device after the outlet relay is set to the "Latching" mode. See
Relay Behavior
(on page 212).
Specifying Non-Critical Outlets
This section applies to outlet-switching capable models only.
This command determines critical and non-critical outlets. It is associated with
the load shedding mode. See
config:#
pdu nonCriticalOutlets <outlets1>:false;<outlets2>:true
Separate outlet numbers and their settings with a colon. Separate each "false"
and "true" setting with a semicolon.
Variables:
<outlets1> is one or multiple outlet numbers to be set as critical outlets.
Use commas to separate outlet numbers.
Use a dash for a range of consecutive outlets. For example, 3-8 represents
outlets 3 to 8.
<outlets2> is one or multiple outlet numbers to be set as NON-critical
outlets. Use commas to separate outlet numbers.
Use a dash for a range of consecutive outlets. For example, 3-8 represents
outlets 3 to 8.
Chapter 9: Using the Command Line Interface
Load Shedding Mode
(on page 229).
PX3TS Latching
573