LEGRAND Raritan PX3TS User Manual page 473

Transfer switch
Table of Contents

Advertisement

Field
Wait time after successful ping
To make the PX3TS declare the inaccessibility of the monitored PDU
when that PDU becomes inaccessible for around 12 seconds (4
seconds * 3 pings), enter the following data.
Field
Wait time after unsuccessful ping
Number of consecutive unsuccessful pings for
failure
To make the PX3TS stop pinging the target PDU for 60 seconds (1
minute) after the PDU inaccessibility is declared, enter the following
data. After 60 seconds, the PX3TS will re-ping the target PDU,
Field
Wait time before resuming pinging after failure
The "Number of consecutive failures before disabling feature (0 =
unlimited)" can be set to any value you want.
5.
Click Create.
Step 2: Create an event rule to send SNMP notifications for the target
PDU
1.
Choose Device Settings > Event Rules.
2.
Click
3.
Select the Enabled checkbox to enable this new rule.
4.
Configure the following.
Field/setting
Rule name
Event
Trigger condition
This will make the PX3TS react only when the target PDU becomes
inaccessible.
5.
Select the System SNMP Notification Action.
Chapter 7: Using the Web Interface
.
Data specified
Send SNMP notifications for PDU
(192.168.84.95) inaccessibility
Choose Server Monitoring > 192.168.84.95 >
Unreachable
Select the Unreachable radio button
Data entered
5
Data entered
4
3
Data entered
60
453