Field
Wait time after successful ping
▪
To make the PX3TS declare the inaccessibility of the monitored PDU
when that PDU becomes inaccessible for around 12 seconds (4
seconds * 3 pings), enter the following data.
Field
Wait time after unsuccessful ping
Number of consecutive unsuccessful pings for
failure
▪
To make the PX3TS stop pinging the target PDU for 60 seconds (1
minute) after the PDU inaccessibility is declared, enter the following
data. After 60 seconds, the PX3TS will re-ping the target PDU,
Field
Wait time before resuming pinging after failure
▪
The "Number of consecutive failures before disabling feature (0 =
unlimited)" can be set to any value you want.
5.
Click Create.
Step 2: Create an event rule to send SNMP notifications for the target
PDU
1.
Choose Device Settings > Event Rules.
2.
Click
3.
Select the Enabled checkbox to enable this new rule.
4.
Configure the following.
Field/setting
Rule name
Event
Trigger condition
This will make the PX3TS react only when the target PDU becomes
inaccessible.
5.
Select the System SNMP Notification Action.
Chapter 7: Using the Web Interface
.
Data specified
Send SNMP notifications for PDU
(192.168.84.95) inaccessibility
Choose Server Monitoring > 192.168.84.95 >
Unreachable
Select the Unreachable radio button
Data entered
5
Data entered
4
3
Data entered
60