Dx2 Sensor Packages - LEGRAND Raritan PX3TS User Manual

Transfer switch
Table of Contents

Advertisement

DX2 Sensor Packages

You can cascade up to 12 DX2 sensor packages.
When cascading DX2, remember that the PX3TS only supports a maximum of
32 sensors and/or actuators.
If there are more than 32 sensors and/or actuators connected, every sensor
and/or actuator after the 32nd one is NOT managed by the PX3TS.
Tip: To manage the last several sensors/actuators after 32nd function, you can
release some "managed" sensors or actuators, and then manually bring the last
several sensors/actuators into management. See
Numbers
Components
RJ-45 ports, each of which is located on either
end of a DX2 sensor package.
LED, which indicates the sensor package's
status
Connect DX2 to the PX3TS:
1.
Connect a standard network patch cable (CAT5e or higher) to either RJ-45
port on a DX2 sensor package.
2.
If you want to cascade DX2 packages, get an additional standard network
patch cable (CAT5e or higher) and then:
a.
Plug one end of the cable into the remaining RJ-45 port on the prior
DX2 package.
b. Plug the other end into either RJ-45 port on an additional DX2
package.
Repeat the same steps to cascade more DX2 packages.
Chapter 4: Connecting External Equipment (Optional)
Peripherals
(on page 258).
43