If you entered the command without "/y", a message appears, prompting you
to confirm the operation. Then:
▪
Type y to confirm the operation, OR
▪
Type n to abort the operation
If you have configured outlet switching sequence and/or delay, PX3TS will
prompt you with one more question:
Should outlet sequence order and delays be used during
switching?
▪
Type y to apply the current outlet sequence and delay settings when
switching on outlets. See
Delay
(on page 226).
▪
Type n to apply the default sequence and delays.
Turning Off the Outlet(s)
This section applies to outlet-switching capable models only.
This command turns off one or multiple outlets.
#
power outlets <numbers> off
To quicken the operation, you can add the parameter "/y" to the end of the
command, which confirms the operation.
#
power outlets <numbers> off /y
Variables:
•
<numbers> is one of the options: all, an outlet number, a list or a range of
outlets.
Option
Description
all
Switches OFF all outlets.
A specific outlet
Switches OFF the specified outlet.
number
A comma-
Switches OFF multiple, inconsecutive or consecutive
separated list of
outlets.
outlets
For example, to specify 7 outlets -- 2, 4, 9, 11, 12, 13
and 15, type:
outlets 2,4,9,11-13,15.
Chapter 9: Using the Command Line Interface
Setting Outlet Power-On Sequence and