Chapter 6 Using The Px3Ts; Power Transfer - LEGRAND Raritan PX3TS User Manual

Transfer switch
Table of Contents

Advertisement

Chapter 6

Power Transfer

Using the PX3TS
In This Chapter
Power Transfer ................................................................................................. 108
Transfer Switch Indicator Lamps ...................................................................... 114
Alarm Indicator Lamps ...................................................................................... 118
Control Push Buttons ........................................................................................ 119
Testing Indicator Lamps .................................................................................... 120
Short Circuit Detection ..................................................................................... 120
Outlets .............................................................................................................. 120
Connection Ports .............................................................................................. 121
Front LCD Display .............................................................................................. 125
Reset Buttons ................................................................................................... 163
Fuses for the Inlet Transfer Switch ................................................................... 164
Overcurrent Protectors for Outlets .................................................................. 167
Beeper .............................................................................................................. 168
Power Cycling the PX3TS .................................................................................. 168
The PX3TS has two inlets: INLET 1 and INLET 2. These inlets are to connect to
diverse power sources. One inlet is configured as the primary (preferred), and
the other is configured as the standby (alternate). The factory default preferred
power source is Inlet 1, and the default alternate source is Inlet 2.
When power is available from both sources and power quality is identical, the
PX3TS selects the preferred inlet to power the load. If a power failure occurs on
the preferred source or its power quality deteriorates below an acceptable
level, the power can be transferred from one inlet to the other automatically or
manually on the PX3TS. Power transfer does not interrupt the operation of the
connected equipment. The transfer time takes only 4-8 milliseconds (1/4 AC
cycle). See the diagram below.