9.
To remove any action(s) from the 'Selected actions' field, click that action's
.
To remove all actions, click Deselect All.
Radio buttons for different events:
According to the event you select, the "Trigger condition" field containing three
radio buttons may or may not appear.
Event types
Radio buttons
Numeric sensor
Available radio buttons include "Asserted,"
threshold-crossing
"Deasserted" and "Both."
events, or the
▪ Asserted: PX3TS takes the action only when the
occurrence of the
selected event -- true
or false
▪ Deasserted: PX3TS takes the action only when
▪ Both: PX3TS takes the action both when the
State sensor state
Available radio buttons include
"Alarmed/Open/On," "No longer
change
alarmed/Closed/Off" and "Both."
▪ Alarmed/Open/On: PX3TS takes the action only
▪ No longer alarmed/Closed/Off: PX3TS takes the
▪ Both: PX3TS takes the action whenever the
Sensor availability
Available radio buttons include "Unavailable,"
"Available" and "Both."
▪ Unavailable: PX3TS takes the action only when
▪ Available: PX3TS takes the action only when the
▪ Both: PX3TS takes the action both when the
Chapter 7: Using the Web Interface
selected event occurs. That is, the status of the
event transits from FALSE to TRUE.
the selected event disappears or stops. That is,
the status of the selected event transits from
TRUE to FALSE.
event occurs (asserts) and when the event
stops/disappears (deasserts).
when the chosen sensor enters the alarmed,
open or on state.
action only when the chosen sensor returns to
the normal, closed, or off state.
chosen sensor switches its state.
the chosen sensor is NOT detected and becomes
unavailable.
chosen sensor is detected and becomes
available.
chosen sensor becomes unavailable or available.
379