Chapter 6: Using the PX3TS
128
Inlet Information
The Inlet mode is displayed as "INLET" on the LCD display. Below illustrates the
inlet information shown on the LCD display.
Section
Example information
The selected target is INLET 1.
This inlet's L1 current reading is 23 amps.
The selected inlet line is L1.
"MASTER" indicates the PX3TS is the master device in a
cascading chain.
For a slave device, it shows "SLAVE" instead.
Note: "MASTER/SLAVE" information is only available in Port
Forwarding mode.
The measurement unit is A (ampere).
To display an inlet's information:
1.
Press the MODE button until the term "INLET" is displayed.
2.
On a multi-inlet model, press the Up or Down button until the desired
inlet's number is displayed at the top.
3.
If your PX3TS is a 3-phase model, the selected inlet line is indicated below
the reading. Press the Up or Down button until the desired inlet line's
number (L1, L2, L3, L1-L2, L2-L3 or L3-L1) is shown.
4.
Press the FUNC button to switch between voltage, active power and
current readings of the selected target.
A is displayed for the current reading. A means Amp.
V is displayed for the voltage reading. V means Volt.
W is displayed for the power reading. W means Watt.
If the word "ALARM" appears below the reading, it means the currently
displayed reading already reaches or crosses the upper or lower
thresholds.