Chapter 9: Using the Command Line Interface
config:#
sensor ts inletPhaseSyncAngle assertionTimeout <as_value>
config:#
sensor inlet 1 current upperWarning 20 lowerWarning 12
678
Variables:
<option> is one of the options: enable, disable or a numeric value.
Option
Description
enable
Enables the specified threshold for the inlet phase
sync angle sensor.
disable
Disables the specified threshold for the inlet phase
sync angle sensor.
A numeric value
Sets a value for the specified threshold of the inlet
phase sync angle sensor and enables this threshold at
the same time.
<hy_value> is a numeric value that is assigned to the hysteresis for the
inlet phase sync angle sensor. See
Hysteresis
(on page 839).
<as_value> is a number in samples that is assigned to the assertion
timeout for the inlet phase sync angle sensor. It ranges between 1 and 100.
See
"To Assert" and Assertion Timeout
Examples
This section illustrates several environmental sensor threshold configuration
examples.
Example 2 - Warning Thresholds for Inlet Sensors
The following command sets both the Upper Warning and Lower Warning
thresholds for the inlet 1 RMS current.
Results:
The Upper Warning threshold for the inlet 1 RMS current is set to 20A. It
also enables the upper warning threshold if this threshold has not been
enabled yet.
The Lower Warning threshold for the inlet 1 RMS current is set to 12A. It
also enables the lower warning threshold if this threshold has not been
enabled yet.
"To De-assert" and Deassertion
(on page 837).