Sensor Threshold Configuration Commands - LEGRAND Raritan PX3TS User Manual

Transfer switch
Table of Contents

Advertisement

defaultThresholds temperature upperWarning 20
config:#
upperCritical 24
config:#
sensor inlet <n> <sensor type> upperCritical <option>
config:#
sensor inlet <n> <sensor type> upperWarning <option>
Example - Default Upper Thresholds for Temperature
It is assumed that your preferred measurement unit for temperature is set to
degrees Celsius. Then the following command sets the default Upper Warning
threshold to 20
and Upper Critical threshold to 24
sensors.

Sensor Threshold Configuration Commands

A sensor configuration command begins with sensor. You can use the
commands to configure the threshold, hysteresis and assertion timeout values
for any sensor associated with the following items:
Inlets
Outlets (only available for models with outlet switching)
Overcurrent protectors
Environmental sensors
Transfer switch sensors
It is permitted to assign a new value to the threshold at any time regardless of
whether the threshold has been enabled.
Commands for Inlet Sensors
A sensor configuration command for inlets begins with sensor inlet.
You can configure various inlet sensor threshold settings at a time by
combining multiple commands. See
Set the Upper Critical threshold for an inlet sensor:
Set the Upper Warning threshold for an inlet sensor:
Set the Lower Critical threshold for an inlet sensor:
Chapter 9: Using the Command Line Interface
for all temperature
Multi-Command Syntax
(on page 695).
669