LEGRAND Raritan PX3TS User Manual page 697

Transfer switch
Table of Contents

Advertisement

config:#
sensor ts inletPhaseSyncAngle upperCritical <option>
config:#
sensor ts inletPhaseSyncAngle upperWarning <option>
config:#
sensor ts inletPhaseSyncAngle lowerCritical <option>
config:#
sensor ts inletPhaseSyncAngle lowerWarning <option>
config:#
sensor ts inletPhaseSyncAngle hysteresis <hy_value>
<hy_value> is a numeric value that is assigned to the hysteresis for the
specified environmental sensor. See
Hysteresis
(on page 839).
<as_value> is a number in samples that is assigned to the assertion
timeout for the specified environmental sensor. It ranges between 1 and
100. See
"To Assert" and Assertion Timeout
Commands for Transfer Switch Sensors
A sensor threshold configuration command for transfer switch sensors begins
with sensor ts. Currently only inlet phase sync angle settings can be configured.
You can configure various inlet phase sync angle settings at a time by
combining multiple commands. See
Set the Upper Critical threshold for the inlet phase sync angle:
Set the Upper Warning threshold for the inlet phase sync angle:
Set the Lower Critical threshold for the inlet phase sync angle:
Set the Lower Warning threshold for the inlet phase sync angle:
Set the deassertion hysteresis for the inlet phase sync angle:
Set the assertion timeout for the inlet phase sync angle:
Chapter 9: Using the Command Line Interface
"To De-assert" and Deassertion
(on page 837).
Multi-Command Syntax
(on page 695).
677