Manual Transfer Scenarios
Manual transfer is prevented in specific scenarios. The following table indicates
when a manual transfer can or cannot be performed. Certain scenarios require
pressing the front panel Alarm Override button in addition to the Manual
Transfer button to perform a manual transfer. See
Alarm is Present
(on page 114).
Make sure the front panel Manual Transfer button has been enabled before
using it. You can verify the button status via the Alarm indicator lamps. See
Alarm Indicator Lamps
(on page 118).
: A power transfer is permitted.
Blank: No power transfer is permitted.
Inactive inlet's status
Power Critical (red
light)
Power Warning
(orange light)
Phase Sync alarm
Overload alarm
Switch open fault
Switch short fault
MOV surge protector
fault
Fuse alarm
12V SMPS fault
Whenever the PX3TS prevents a manual transfer from being performed, it is
disabled across all interfaces, including the front panel button, web interface
and CLI command.
Note: Switch open/short, MOV, 12V SMPS faults are internal transfer switch
faults, causing the Internal Failure indicator lamp on the front panel to turn on.
See
Alarm Indicator Lamps
Manual Transfer When an
Manual Transfer
(on page 118).
Chapter 6: Using the PX3TS
Alarm Override +
Manual Transfer
113