LEGRAND Raritan PX3TS User Manual page 454

Transfer switch
Table of Contents

Advertisement

Chapter 7: Using the Web Interface
434
After the new action is created, follow the procedure below to create an event
rule that triggers the load shedding mode when the contact closure sensor
enters the alarmed state. This event rule involves the following:
Event: Peripheral Device Slot > Slot 1 > State Sensor/Actuator >
Alarmed/Open/On
Trigger condition: Alarmed
Action: Activate Load Shedding
Step 2: create the contact closure-triggered load shedding event rule
1.
Click
2.
In this illustration, assign the name "Contact Closure Triggered Load
Shedding" to the new rule.
3.
In the Event field, select "Peripheral Device Slot" to indicate we are
specifying an event related to the environmental sensor package.
4.
Select the ID number of the desired contact closure sensor. In this
illustration, the ID number of the desired contact closure sensor is 1, so
select Slot 1.
Note: ID numbers of all sensors/actuators are available on the Peripherals
page. See
Peripherals
5.
Select "State Sensor/Actuator" because the contact closure sensor is a
state sensor.
6.
Select "Alarmed" since we want the PX3TS to respond when the selected
contact closure sensor changes its state related to the "alarmed" state.
7.
In the 'Trigger condition' field, select the Alarmed/Open/On radio button
so that the action is taken only when the contact closure sensor enters the
alarmed state.
on the Event Rules page.