Advertisement

4.
Once complete, information of both installed and uploaded firmware
versions as well as compatibility and signature-checking results are
displayed.
If anything is incorrect, click Discard Upload.
5.
To proceed with the update, click Update Firmware.
Warning: Do NOT power off the PX3TS during the update.
6.
During the firmware update:
A progress bar appears on the web interface, indicating the update
status.
The front panel display shows the firmware upgrade message. See
Showing the Firmware Upgrade Progress
The outlet LEDs flash if the relay boards are being updated. If the
firmware update does not include the update of the relay board
firmware, outlet LEDs do NOT flash.
No users can successfully log in to the PX3TS.
Other users' operation, if any, is forced to suspend.
7.
When the update is complete, the PX3TS resets, and the Login page
re-appears.
Other logged-in users are logged out when the firmware update is
complete.
Important: If you are using the PX3TS with an SNMP manager, download its
MIB again after the firmware update to ensure your SNMP manager has the
correct MIB for the latest release you are using. See Using SNMP (on page
515).
Alternatives:
To use a different method to update the firmware, refer to:
Firmware Update via SCP
Bulk Configuration or Firmware Upgrade via DHCP/TFTP
Firmware Upgrade via USB
Chapter 7: Using the Web Interface
(on page 162).
(on page 711)
(on page 744)
(on page 746)
475

Advertisement