config:#
sensor ocp 2 current upperWarning enable upperCritical 16
Example 1 - Upper Critical Threshold for a Temperature Sensor
The following command sets the Upper Critical threshold of the environmental
"temperature" sensor with the ID number 2 to 40 degrees Celsius. It also
enables the upper critical threshold if this threshold has not been enabled yet.
config:#
sensor externalsensor 2 temperature upperCritical 40
Example 3 - Upper Thresholds for Overcurrent Protector Sensors
The following command sets both the Upper Critical and Upper Warning
thresholds for the 2nd overcurrent protector.
Results:
The Upper Critical threshold for the 2nd overcurrent protector's RMS
current is set to 16A. It also enables the upper critical threshold if this
threshold has not been enabled yet.
The Upper Warning threshold for the 2nd overcurrent protector's RMS
current is enabled.