To configure the thresholds of total active energy and power:
Click the "Thresholds" section if you want to configure thresholds for total
active energy and total active power. See
Energy or Power
(on page 215).

Internal Beeper State

The PDU page indicates the internal beeper state.
Available beeper states:
States
Description
Off
The beeper is turned off.
Active
The beeper is turned on.
"Activation Reason" is displayed, indicating why the
beeper sounds an alarm.
For example, if the beeper is turned on because of a
specific event rule "XXX," the activation reason looks
like:
Event Action triggered by rule: XXX
Scenarios when the beeper sounds an alarm:
Any overcurrent protector on the PX3TS, including fuses and circuit
breakers, has tripped or blown. See
You have set an event rule that turns on the internal beeper when a
specific event occurs, and that event occurs now. See
Actions
(on page 375).
On the PX3TS supporting residual current monitoring (RCM), the beeper
also sounds when an RCM alarm is detected.
Note that only the RCM sensor will cause the PDU to beep while RCM "DC"
sensor does not cause the PDU to beep regardless of its sensor state.
For details, see PX3TS Models with Residual Current Monitoring.
Tip: To check the internal beeper state via CLI, see
536).
Chapter 7: Using the Web Interface
Setting Thresholds for Total Active
Beeper
(on page 168).