LEGRAND Raritan PX3TS User Manual page 702

Transfer switch
Table of Contents

Advertisement

Chapter 9: Using the Command Line Interface
config:#
serverReachability modify <n> ipAddress <IP_host>
682
<succ_ping> is the number of successful pings for declaring the monitored
device "Reachable." Valid range is 0 to 200.
<fail_ping> is the number of consecutive unsuccessful pings for declaring
the monitored device "Unreachable." Valid range is 1 to 100.
<succ_wait> is the wait time to send the next ping after a successful ping.
Valid range is 5 to 600 (seconds).
<fail_wait> is the wait time to send the next ping after a unsuccessful ping.
Valid range is 3 to 600 (seconds).
<resume> is the wait time before the PX3TS resumes pinging after
declaring the monitored device "Unreachable." Valid range is 5 to 120
(seconds).
<disable_count> is the number of consecutive "Unreachable" declarations
before the PX3TS disables the ping monitoring feature for the monitored
device and returns to the "Waiting for reliable connection" state. Valid
range is 1 to 100 or unlimited.
Deleting a Monitored Device
This command removes a monitored IT device from the server reachability list.
config:#
serverReachability delete <n>
Variables:
<n> is a number representing the sequence of the IT device in the
monitored server list.
You can find each IT device's sequence number using the CLI command of
show serverReachability as illustrated below.
Modifying a Monitored Device's Settings
The command to modify a monitored IT device's settings begins with
serverReachability modify.
You can modify various settings for a monitored device at a time. See
Multi-Command Syntax
Modify a device's IP address or host name:
Enable or disable the ping monitoring feature for the device:
(on page 695).