Using the Reset Button

Resetting to Factory Defaults
You can use either the reset button or the command line interface (CLI) to reset
the PX3TS.
Important: Exercise caution before resetting the PX3TS to its factory defaults.
This erases existing information and customized settings, such as user profiles,
threshold values, and so on. Only active energy data and firmware upgrade
history are retained.
Alternative:
Another method to reset it to factory defaults is to use the web interface. See
Resetting All Settings to Factory Defaults
In This Chapter
Using the Reset Button ..................................................................................... 775
Using the CLI Command .................................................................................... 776
The reset button described in this section is the one near the LCD display.
An RS-232 serial connection to a computer is required for using the reset
button.
To reset to factory defaults using the reset button:
1.
Connect a computer to the PX3TS. See
Computer
(on page 23).
2.
Launch a terminal emulation program such as Kermit or PuTTY, and open a
window on the PX3TS. For information on the serial port configuration, see
Step 2 of
Initial Network Configuration via CLI
3.
Press (and release) the Reset button of the PX3TS device while pressing the
Esc key of the keyboard several times in rapid succession. A prompt (=>)
should appear after about one second.
4.
Type defaults to reset the PX3TS to its factory defaults.
5.
Wait until the reset is complete.
(on page 491).
Connecting the PX3TS to a
(on page 851).
775