Setting Thresholds for Total Active Energy or Power

This section applies only to multi-inlet models, including in-line monitors.
Thresholds for total active energy and total active power are disabled by
default. You can enable and set them so that you are alerted when the total
active energy or total active power hits a certain level.
For a regular PX3TS model with multiple inlets:
Total active energy = sum of all inlets' active energy values
Total active power = sum of all inlets' active power values
For an in-line monitor with multiple inlets/outlets:
Total active energy = sum of all outlets' active energy values
Total active power = sum of all outlets' active power values
To configure thresholds for total active energy and/or power:
1.
Click PDU.
On the PDU page, you can also view the total active power and total
active energy. See
2.
Click the Thresholds title bar at the bottom of the page to display
thresholds.
3.
Click the desired sensor (required), and then click Edit Thresholds.
4.
Make changes as needed.
To enable any threshold, select the corresponding checkbox.
Chapter 7: Using the Web Interface
PDU
(on page 206).
215