Outlet Sensor Threshold Information - LEGRAND Raritan PX3TS User Manual

Transfer switch
Table of Contents

Advertisement

Chapter 9: Using the Command Line Interface
544

Outlet Sensor Threshold Information

This command syntax shows the specified outlet sensor's threshold-related
information.
#
show sensor outlet <n> <sensor type>
To show detailed information, add the parameter "details" to the end of the
command.
#
show sensor outlet <n> <sensor type> details
Variables:
<n> is the number of the outlet whose sensors you want to query.
<sensor type> is one of the following sensor types:
Sensor type
current
voltage
activePower
apparentPower
powerFactor
activeEnergy
lineFrequency
Displayed information:
Without the parameter "details," only the sensor reading, state, threshold,
deassertion hysteresis and assertion timeout settings of the specified
outlet sensor are displayed.
With the parameter "details," more sensor information is displayed,
including resolution and range.
If the requested sensor type is not supported, the "Sensor is not available"
message is displayed.
Description
Current sensor
Voltage sensor
Active power sensor
Apparent power sensor
Power factor sensor
Active energy sensor
Line frequency sensor