Appendix C: Configuration or Firmware Upgrade with a USB Drive
736
•
The default value is serial:1, making the PX3TS search for its serial
number in the first column.
•
This option is used only if the "device_list" option has been set.
factory_reset
•
If this option is set to true, the PX3TS will be reset to factory defaults.
•
If the device configuration will be updated at the same time, the factory
reset will be executed before updating the device configuration.
bulk_config_restore
•
Specify the name of the bulk configuration file used to configure or restore
the PX3TS.
Note: See
Bulk Configuration
a bulk configuration file.
•
Additional configuration keys set via the config.txt file will be applied after
performing the bulk restore operation.
•
This option CANNOT be used with the option "full_config_restore."
•
If a firmware upgrade will be performed at the same time, you must
generate the bulk configuration file based on the NEW firmware version
instead of the current firmware version.
full_config_restore
•
Specify the name of the full configuration backup file used to restore the
PX3TS.
Note: See
Backup and Restore of Device Settings
instructions on generating the full configuration backup file.
•
Additional configuration keys set via the config.txt file will be applied after
performing the configuration restore operation.
•
This option CANNOT be used with the option "bulk_config_restore."
•
If a firmware upgrade will be performed at the same time, you must
generate the full configuration backup file based on the NEW firmware
version instead of the current firmware version.
collect_diag
•
If this option is set to true, the diagnostic data of the PX3TS is
transmitted to the USB drive.
•
The filename of the diagnostic data written into the USB drive is:
diag_<unit-serial>.zip
(on page 479) for instructions on generating
(on page 486) for