Chapter 9: Using the Command Line Interface
576
Enabling or Disabling Peripheral Device Auto Management
This command enables or disables the Peripheral Device Auto Management
feature.
config:#
pdu peripheralDeviceAutoManagement <option>
Variables:
<option> is one of the options: enable or disable.
Option
Description
enable
Enables the automatic management feature for
environmental sensor packages.
disable
Disables the automatic management feature for
environmental sensor packages.
For more information, see
(on page 214)..
Setting the Maximum Number of Active Powered Dry Contact Actuators
This command determines the upper limit of "active" powered dry contact
actuators on one PX3TS device. You need either 'Change Peripheral Device
Configuration' privilege or 'Administrator Privileges' to change its upper limit.
config:#
pdu activePoweredDryContactLimit <number>
Variables:
<number> is the number representing the maximum number of active
powered dry contact actuators. Its value ranges between 0 to 24.
Note: An "active" actuator is the one that is turned ON, or, if with a door handle
connected, is OPENED.