Bulk Configuration for Outlet Thresholds

Outlet thresholds, if enabled, help you identify whether any outlet enters the
warning or critical level. See
In addition, you can have PX3TS automatically generate alert notifications for
any warning or critical status. See
Thresholds of multiple or all outlets can be configured simultaneously on the
Outlets page.
Per default, there are pre-defined RMS voltage and current threshold values in
related fields. See
Default Voltage and Current Thresholds
To configure thresholds-related settings for multiple outlets:
1.
On the Outlets page, click
2.
In the "Show Outlet Sensors of Type" field, select a sensor type.
3.
Select one or multiple outlets.
To select ALL outlets, select the topmost checkbox in the header row.
4.
Click Edit Thresholds.
5.
Make changes as needed.
To enable any threshold, select the corresponding checkbox.
Chapter 7: Using the Web Interface
Yellow- or Red-Highlighted Sensors
Event Rules and Actions
> Threshold Bulk Setup.