Power Transfer Settings

The following are the factory-default transfer settings:
The front panel Manual Transfer button is enabled.
Automatic retransfer is enabled.
Wait time prior to performing automatic retransfer is set to 15 seconds.
Perform automatic retransfer only when inlets are in phase.
These default behaviors can be changed by modifying the following fields.
Field
Name
Description
Indicates whether each inlet's MOV surge protector
works properly.
▪ If fine, "OK" is displayed.
▪ Otherwise, "fault" is displayed. In this case,
contact Raritan for Return Merchandize
Authorization (RMA) to fix the issue.
The transfer switch receives DC 12V power from
either inlet. The transfer switch works fine as long as
one of the 12V power supplies works properly.
This +12V status field indicates whether each inlet's
12V power supply to the transfer switch functions
properly.
▪ If fine, "OK" is displayed.
▪ Otherwise, "fault" is displayed. In this case,
contact Raritan for Return Merchandize
Authorization (RMA) to fix the issue.