Chapter 3: Initial Installation and Configuration
38

Power-Sharing Configurations and Restrictions

When either PX3TS PDU enters the power-sharing mode, BOTH PDUs involved
in the power-sharing connection support "less" external equipment than usual.
It is strongly recommended to remove specific equipment from both PX3TS
PDUs when making a power-sharing connection.
Configuration limitations on "both" PDUs:
NO USB wireless LAN adapter is connected.
That is, you have to connect both PDUs to a "wired" network if LAN access
is wanted.
No asset management strips can be connected simultaneously.
The maximum number of DX environmental sensor packages or door
handles that can be connected decreases. For details, see
Sensor Configurations for Power Sharing
After either PDU enters the power-sharing mode, you must NOT physically
remove or add any environmental sensor packages to BOTH PDUs.
Supported
(on page 39).