PDU Linking in the Web GUI

78
How are firmware updates handled?
Uploaded firmware images in the GUI are automatically distributed to all link
units at the same time. Starting a firmware update requires the same image to
be uploaded to all units.
Does PDU Linking support mass deployment of PDUs?
Yes, mass deployment has been extended to support a setup for the PDU
Linking feature (multi-IP or single-IP) via the Raritan Mass Deployment Utility,
which provides the Excel spreadsheet process used for PDU bulk configuration.
For information about using the utility, see
Upgrade with a USB Drive
Which network setup modes are supported by PDU Linking?
For the underlying network, the PDU Linking feature can use the typical
network setup modes:
Independent PDU Setup: All PDUs have their own regular IP address. They
don't need to be in a physical chain to be logically chained. You communicate
only to the master using its normal IP address. Configure networking of the
units, and then add link units using the Web GUI, CLI, or USB.
Bridged Setup: Same as Independent PDU Setup, but the PDUs are physically
connected as a chain, either by ethernet or USB. The configuration steps are
the same as with Independent PDU Setup.
Port Forwarding Cascade: The PDUs are physically connected as a chain (either
by Ethernet or USB). Only the first master PDU is connected to your network
with the IP address you assigned. The other PDUs will get
automatically-assigned private IP addresses which are not visible; you can
configure both PDUs at one time with a USB stick, or configure the network
first and then add link units.
Note: When referring to "cascading", or the physical chaining of units, although
the mixing of connection types (Ethernet and USB) is not recommended in the
cascade, the mixing is possible with these restrictions: In Port Forwarding mode,
you must build a single, linear chain where each unit has exactly one upstream
device and optionally one downstream device. In Bridging mode, you must not
build any loops; in other words, multiple paths between two units.
The following topics describe how to configure and use PDU Linking using the
web interface.