Field
Function
Name
Customizes the device name.
*Relay behavior on
Selects an operating mode to determine
power loss
the latching relay behavior when PDU
power is lost.
▪ Options: Non-latching and Latching
▪ Non-latching has all relays open at
*Outlet state on
Determines the initial power state of ALL
device startup
outlets after the PX3TS powers up.
▪ Options: on, off, and last known
(for non-latching
mode only)
See
(on page 212).
Click
to select an option.
Adjust the numeric values.
Select or deselect the checkbox.
For time-related fields, if you do not prefer the option selection using
, you can type a value manually which must include a time unit,
such as '50 s'. See
In the following table, those fields marked with * are available on an
outlet-switching capable model only.
the power loss while latching has all
relays remain unchanged at the
power loss.
Options for Outlet State on Startup
Chapter 7: Using the Web Interface
Time Units
(on page 214).
Note
See
PX3TS Latching Relay Behavior
page 212).
▪ After removing power from the PDU,
you must wait for a minimum of 10
seconds before powering it up again.
Otherwise, the default outlet state
settings may not work properly.
▪ You can override the global outlet
state setting on a per-outlet basis so
specific outlets behave differently on
startup. See
(on page 232).
▪ This setting works only when 'Relay
behavior on power loss' is set to
Non-latching. This is because all
relays keep their states unchanged in
the latching mode regardless of the
power supply status.
(on
Individual Outlet Pages
207