Before You Begin

1. Prepare the installation site. Make sure the installation area is clean and not exposed to extreme temperatures or humidity. Allow sufficient
space around the device for cabling and outlet connections. Safety instructions are provided in the PXC/PXO online help.
Fill out the Equipment Setup Worksheet found in the online help. Record the model, serial number, and use of each IT device connected to the
PDU's power outlets.
QS Rule

Mounting the PDU

Use one of the mounting methods to install your product.

Circuit Breaker Orientation Limitation

Usually a PDU can be mounted in any orientation. However, when mounting a PDU with circuit breakers, you must follow these rules:
Circuit breakers CANNOT face down. For example, do not horizontally mount a Zero U PDU with circuit breakers facing up or down.
PXC Rackmount Methods
The proper PXC rackmount method is model dependent.
Mounting Zero U Models with Mount Buttons
1. Turn to the rear of the PXC.
2. Align and slide the Raritan-provided mounting button to the rear rail of the PDU.
3. Turn the button clockwise until it is securely locked in place.
PXC_PXO Quick Setup Guide
PXC_PXO_QSG_A1_4.0.10  255-80-0059-00 RoHS