Configuring Environmental Sensors' Default Thresholds - LEGRAND Raritan PX3TS User Manual

Transfer switch
Table of Contents

Advertisement

config:#
defaultThresholds <sensor type> upperCritical <value>
config:#
defaultThresholds <sensor type> upperWarning <value>
config:#
defaultThresholds <sensor type> lowerCritical <value>
config:#
defaultThresholds <sensor type> lowerWarning <value>
Example 1 - Environmental Sensor Naming
The following command assigns the name "Cabinet humidity" to the
environmental sensor with the ID number 4.
config:#
externalsensor 4 name "Cabinet humidity"
Example 2 - Sensor Threshold Selection
The following command sets the environmental sensor #1 to use the default
thresholds, including the deassertion hysteresis and assertion timeout, as its
threshold settings.
config:#
externalsensor 1 useDefaultThresholds true

Configuring Environmental Sensors' Default Thresholds

You can set the default values of upper and lower thresholds, deassertion
hysteresis and assertion timeout on a sensor type basis, including temperature,
humidity, air pressure and air flow sensors. The default thresholds
automatically apply to all environmental sensors that are newly detected or
added.
A default threshold configuration command begins with defaultThresholds.
You can configure various default threshold settings for the same sensor type
at a time by combining multiple commands. See
page 695).
Set the Default Upper Critical Threshold for a specific sensor type:
Set the Default Upper Warning Threshold for a specific sensor type:
Set the Default Lower Critical Threshold for a specific sensor type:
Set the Default Lower Warning Threshold for a specific sensor type:
Set the Default Deassertion Hysteresis for a specific sensor type:
Chapter 9: Using the Command Line Interface
Multi-Command Syntax