Chapter 7: Using the Web Interface
Field
Altitude
Active powered dry
contact limit
262
Function
Specifies the altitude of PX3TS above sea
level when a Raritan's differential air
pressure sensor is attached.
▪ Range: -425 to 3000 meters (-1394 to
9842 feet)
▪ Note that it can be a negative value
down to -425 meters (-1394 feet)
because some locations are below the
sea level.
Determines the maximum number of
"active" powered dry contact actuators
that is permitted concurrently.
▪ Range: 0 to 24
▪ Default: 1
3.
Click Save.
4.
To return to the sensor list on the Peripheral Devices page, click
"Peripheral Devices" on the top.
To configure default threshold settings:
Note that any changes made to default threshold settings not only
re-determine the initial threshold values that will apply to newly-added sensors
but also the threshold values of the already-managed sensors where default
thresholds are being applied. See
273).
1.
Click
> Default Threshold Setup.
Note
▪ The device's altitude is associated
with the altitude correction factor.
See
Altitude Correction Factors
page 844).
▪ The default altitude measurement
unit is meter. See
Measurement Units
▪ You can have the measurement unit
vary between meter and foot
according to user credentials. See
Setting Your Preferred Measurement
Units
(on page 305).
▪ An "active" actuator is the one that is
turned ON, or, if with a door handle
connected, is OPENED.
▪ This setting only applies to "powered
dry contact" (PD) actuators rather
than normal "dry contact" actuators.
▪ You need either 'Change Peripheral
Device Configuration' privilege or
'Administrator Privileges' to change
its upper limit.
▪ To turn on/off the connected
actuators, see
Peripherals
258).
Individual Sensor/Actuator Pages
(on
Setting Default
(on page 306).
(on page
(on page