Chapter 7: Using the Web Interface
Field
*Outlet initialization
delay on device
startup
(for non-latching
mode only)
*Power off period
during power cycle
*Inrush guard delay Prevents a circuit breaker trip due to
208
Function
Determines how long the PX3TS waits
before providing power to all outlets
during power cycling or after recovering
from a temporary power loss.
▪ Range: 1 second to 1 hour
Determines the power-off period after
the outlet is switched OFF during a power
cycle.
▪ Range: 1 second to 1 hour
inrush current when many devices
connected to the PDU are turned on.
▪ Range: 100 milliseconds to 10 seconds
3.
Click Save.
To reset ALL active energy counters:
An active energy reading is a value of total accumulated energy, which is never
reset, even if the power fails or the PX3TS is rebooted. However, you can
manually reset this reading to restart the energy accumulation process.
Only users with the "Admin" role assigned can reset active energy readings.
Note: This reset button does not reset the active energy values of outlet groups.
See
Outlet Groups
(on page 239).
1.
Click
2.
Click Reset on the confirmation message.
All active energy readings on this PX3TS are reset to zero.
Note
▪ See
Initialization Delay Use Cases
page 213).
This setting works only when 'Relay
behavior on power loss' is set to
Non-latching. This is because all
relays keep their states unchanged in
the latching mode regardless of the
power supply status.
▪ Power cycling the outlet(s) turns the
outlet(s) off and then back on.
▪ You can override this global power
cycle setting on a per-outlet basis so
specific outlets' power-off period is
different. See
(on page 232).
See
Inrush Current and Inrush Guard
Delay
(on page 213).
.