Energywise Configuration Commands - LEGRAND Raritan PX3TS User Manual

Transfer switch
Table of Contents

Advertisement

Chapter 9: Using the Command Line Interface
config:#
serverReachability modify 2 numberOfSuccessfulPingsToEnable 10
numberOfUnsuccessfulPingsForFailure 8
waitTimeAfterSuccessfulPing 30
684
<succ_number> is the number of successful pings for declaring the
monitored device "Reachable." Valid range is 0 to 200.
<fail_number> is the number of consecutive unsuccessful pings for
declaring the monitored device "Unreachable." Valid range is 1 to 100.
<succ_wait> is the wait time to send the next ping after a successful ping.
Valid range is 5 to 600 (seconds).
<fail_wait> is the wait time to send the next ping after a unsuccessful ping.
Valid range is 3 to 600 (seconds).
<resume> is the wait time before the PX3TS resumes pinging after
declaring the monitored device "Unreachable." Valid range is 5 to 120
(seconds).
<disable_count> is the number of consecutive "Unreachable" declarations
before the PX3TS disables the ping monitoring feature for the monitored
device and returns to the "Waiting for reliable connection" state. Valid
range is 1 to 100 or unlimited.
Example - Server Settings Changed
The following command modifies several ping monitoring settings for the
second server in the server reachability list.

EnergyWise Configuration Commands

An EnergyWise configuration command begins with energywise.
Enabling or Disabling EnergyWise
This command syntax determines whether the Cisco
implemented on the PX3TS is enabled.
config:#
energywise enabled <option>
Variables:
<option> is one of the options: true or false.
Option
Description
true
The Cisco EnergyWise feature is enabled.
EnergyWise endpoint
®